Gas storage Debottlenecking - France

In 2015, Kelvion Thermal Services were contacted by a French Gas Storage site, who were facing cooling capacity issues with their Gas Cooler, especially during summer time when ambient temperatures are extremely high.

After performing a site audit to measure the actual performance of the Gas Cooler, the following was observed by Kelvion
â–º Airflow was found to be 25% lower than design,
â–º Coolers were designed for relatively low ambient temperature (30°C versus a maximum of 37°C for this region)

Kelvion Servies modified the Gas Cooler by upgrading the following parts:
â–º Complete fan set
â–º New motor and gearbox
â–º New fan shaft with top and bottom bearings
â–º New anti-rotating device
â–º New electrical cabinet

Results:
After upgrading the coolers, new site measurements showed that airflow was increased by 35% and the outlet process temperature decreased by 4°C - 5°C.
End-user was fully satisfied with the revamp, being able to operate the coolers without any issues during the summer time.